Skip to main content

Extension

Aeration System Design for Cone-Bottom Round Bins

Before attempting to select, design or manage an aeration system, you should study the following publication: BAE-1101 “Aeration and Cooling of Stored Grain.”

Fact Sheet BAE-1101  discusses the importance of choosing the right airflow rate to obtain the desired aeration system capabilities. Power requirements, fan selection, control systems, and management suggestions are also explained.

This fact sheet presents information for the design or selection of aeration system components for cone-bottom round grain bins.

Cone-bottom bins have the advantage of complete and easy unloading. The cone also provides additional storage capacity in the bin.

Below-grade cone-shaped foundations can only be used in areas of low water tables. If the water table rises to the level of the cone, water may enter the cone and cause grain spoilage.

When only dry grain will enter the bin, a cone slope of 37° or 3 feet fall in a 4 foot run will allow complete unloading. When wet grain will be handled through the bin, the cone slope should be 45° or 1 foot fall in a run of 1 foot.

Aeration Systems

A typical aeration system for a cone-bottom round grain bin is shown in Figure 1. Round metal ducts are used to dis­tribute air in cone-bottom bins. The upper section of the duct is non-perforated with lower sections perforated. The bottom of the duct is usually open.

If a single duct does not have sufficient surface area to avoid excessive operating pressures, a second fan and duct are added as shown in Figure 1, with the air volume divided between the two fans. In large bins, three or more fans and ducts are sometimes required to deliver high airflow rates. In general, centrifugal fans with backward-inclined blades are required to deliver efficient air volumes when operating against the higher static pressures encountered in cone-bottom bins.

Aeration system for a cone-bottom round grain bin.

Figure 1. Aeration system for a cone-bottom round grain bin.

Description of Terms

The following terms are used in the design procedure:

fpm = feet per minute, air velocity; 

CFM = cubic feet of air per minute, air volume; 

CFM/bu = cubic feet of air per minute per bushel, airflow rate

 

Static pressure is the pressure against which the fan must operate, expressed as inches of water.

Design Procedure

The design procedure for aeration systems involves:

  1. Determining bin capacity, selecting air-flow rate, and determining total air volume to be delivered; 
  2. Selecting ducts on the basis of surface area; 
  3. Determining operating static pressure; and 
  4. Selecting fans to deliver the required air volume when operating against the expected static pressure.

Determining Bin Capacity and Air-Flow Volume

Bin capacity is the number of bushels which can be stored in the bin plus the number which can be stored in the cone. The capacity of the bin with and without the cone can be determined from Table 1.  Bin capacity does not include storage in the roof section.

Example:Consider a 30 feet diameter bin with 19 foot sidewalls and a 45° concrete cone shaped foundation. The bin capacity with and without the cone can be found using Table 1. In addition to individual capacities, Table 1 gives the total capacity, bin plus cone. From Table 1, bin capacity without cone is 10,775 bu. The capacity of a 30-foot diameter, 45° cone is 2,820 bu. Therefore total capacity, bin plus cone, is 13,595 bu.  Table 1 can be used for bins with concrete cone shaped foundations and for steel hopper bottom bins.

It is best to aerate the grain with 1/5 cfm/bu (0.2 cfm/bu).  The total airflow requirement would be 0.2 cfm/bu multiplied by the total bushels in the bin.

0.2 cfm/bu x 13,595 bu = 2719 cfm 

Table 1.  Bin Capacity with/without cone.

Diameter (ft.)Height (ft.) Bin Capacity (bu)Capacity due to Cone (bu)
45o cones
Capacity due to Cone (bu)
37o cones
Total Capacity (Bin+Cone),bu
45o cones
Total Capacity (Bin+Cone),bu
37o cones
158112536327014881395
 13185036327022132120
 16227536327026382545
1811225061045028602700
 13265061045032603100
 16327561045038853725
 21430061045049104750
2113362596072045854345
 16445096072054105170
 24667596072076357395
241658251440108072656905
 1969001440108083407980
 24872514401080101659805
 3211625144010801306512705
27198750206015401081010290
 2411025206015401308512565
 3214725206015401678516265
301910775282021201359512895
 2413625282021201644515745
 3218175282021202099520295
332416475385028902032519365
 2718550385028902240021440
 3221975385028902582524865
362419625488036602450523285
 2722075488036602695525735
 3226150488036603103029810
 4032700488036603758036360
422730050631547353636534785
 3235600631547354191540335
 4044500631547355081549235
 4853425631547355974058160
482739250775058104700045060
 3246500775058105425052310
 4058150775058106590063960
 4869775775058107752575585

Table 2 gives the maximum length of duct which may be placed down one side of the cone foundation for various bin diameters and the two cone slopes.

Table 2. Duct Lengths for Cone-Shaped Foundations or Bottoms.

Bin Diameter
(ft.)
45 o cones
1 in 1 slope
Max. length of duct (ft.)
37 o cones
3 in 4 slope
Max. length of duct (ft.)
1498
159.759
181210
211412
241614
271816
302018
362421
422825

Example: For a 30 ft. diameter bin with 45° cone shaped bottom, the maximum length of a duct is 20 feet (using Table 2).

As shown in Figure 1, the air makes a turn when it leaves the fan and transition and enters the duct. This air turbulence is accompanied by an increase in static pressure in the initial section of the duct. For this reason, the initial section of the duct should be non-perforated for a distance equal to twice the duct diameter.

Max. length of duct (Table 2) – (2 x the duct diameter) = max. length of perforated duct

Example: If a 12 inch diameter duct is to be used in our example bin (30 ft. diameter bin), the maximum length of perforated duct is 18 ft.

12 inches = 1 ft.
20 ft. (from Table 2) – (2 x 1 ft.) (1 ft. is the duct diameter) = 18 ft

If an 18 inch (1.5 ft.) diameter duct is to be used, the maximum length of perforated duct is 17 ft.:

20 ft. – (2 x 1.5 ft.) = 17 ft.

Determining Air Velocity through the Grain

Table 3 and Table 4 are used to determine total air volume and the air velocity through the grain when the desired airflow rate is known.  Table 3 is for 45 degree cones and Table 4 is for 37 degree cones. The choice of airflow rate is an important deci­sion. Higher aeration airflow rates give greater management flexibility and may allow the storage of grain with higher moisture content because the grain can be cooled and dried with natural air quicker. However, higher aeration airflow rates also require larger ducts, involve higher static pressures, and have greater power requirements. For a complete discussion of airflow rates, see BAE-1101.

Table 3 (Part A : Total Air Volume (cfm) ). Total air volume and air velocity through the grain for grain bins with 45 degree cones.

         
   Total Air Volume (cfm)
   Air Flow Rate (cfm/bu)
Diameter (ft.)Height (ft.)Total Capacity
(Bin+Cone), bu
1/21/31/41/51/101/20
158148874449637229814974
 1322131107738553443221111
 1626381319879660528264132
181128601430953715572286143
 13326016301087815652326163
 16388519431295971777389194
 214910245516371228982491246
21134585229315281146917459229
 1654102705180313531082541271
 2476353818254519091527764382
241672653633242218161453727363
 1983404170278020851668834417
 241016550833388254120331017508
 321306565334355326626131307653
27191081054053603270321621081541
 241308565434362327126171309654
 321678583935595419633571679839
30191359567984532339927191360680
 241644582235482411132891645822
 32209951049869985249419921001050
3324203251016367755081406520331016
 27224001120074675600448022401120
 32258251291386086456516525831291
3624245051225381686126490124511225
 27269551347889856739539126961348
 323103015515103437758620631031552
 403758018790125279395751637581879
42273636518183121229091727336371818
 3241915209581397210479838341922096
 40508152540816938127041016350822541
 48597402987019913149351194859742987
482747000235001566711750940047002350
 32542502712518083135631085054252713
 40659003295021967164751318065903295
 48775253876325842193811550577533876

Table 3 (Part B : Air Velocity (fpm) ).Total air volume and air velocity through the grain for grain bins with 45 degree cones.

         
   Air Velocity (fpm)
   Air Flow Rate (cfm/bu)
Diameter (ft.)Height (ft.)Total Capacity
(Bin+Cone), bu
1/21/31/41/51/101/20
15814884.212.812.111.680.840.42
 1322136.264.183.132.511.250.63
 1626387.474.983.732.991.490.75
181128605.623.752.812.251.120.56
 1332606.414.273.22.561.280.64
 1638857.645.093.823.051.530.76
 2149109.656.434.833.861.930.97
211345856.624.413.312.651.320.66
 1654107.815.213.913.131.560.78
 24763511.037.355.514.412.211.1
241672658.035.364.023.211.610.8
 1983409.226.154.613.691.840.92
 241016511.247.495.624.52.251.12
 321306514.459.637.225.782.891.44
2719108109.446.34.723.781.890.94
 241308511.437.625.724.572.291.14
 321678514.679.787.335.872.931.47
3019135959.626.414.813.851.920.96
 241644511.647.765.824.662.331.16
 322099514.869.917.435.942.971.49
33242032511.897.935.944.762.381.19
 272240013.18.736.555.242.621.31
 322582515.110.077.556.043.021.51
36242450512.048.036.024.822.411.2
 272695513.258.836.625.32.651.32
 323103015.2510.177.636.13.051.53
 403758018.4712.319.237.393.691.85
42273636513.138.756.575.252.631.31
 324191515.1310.097.576.053.031.51
 405081518.3512.239.177.343.671.83
 485974021.5714.3810.798.634.312.16
48274700012.998.666.55.22.61.3
 325425015107.5631.5
 406590018.2212.159.117.293.641.82
 487752521.4314.2910.728.574.292.14
 

Table 4 (Part A : Total Air Volume (cfm) ). Total air volume and air velocity through the grain for grain bins with 37 degree cones. 

         
   Total Air Volume (cfm)
   Air Flow Rate (cfm/bu)
Diameter (ft.)Height (ft.)Total Capacity
 (Bin+ Cone), bu
1/21/31/41/51/101/20
158139569846534927914070
 1321201060707530424212106
 1625451273848636509255127
181127001350900675540270135
 13310015501033775620310155
 16372518631242931745373186
 214750237515831188950475238
21134345217314481086869435217
 1651702585172312931034517259
 2473953698246518491479740370
241669053453230217261381691345
 1979803990266019951596798399
 2498054903326824511961981490
 321270563534235317625411271635
27191029051453430257320581029515
 241256562834188314125131257628
 321626581335422406632531627813
30191289564484298322425791290645
 241574578735248393631491575787
 32202951014867655074405920301015
33241936596836455484138731937968
 27214401072071475360428821441072
 32248651243382886216497324871243
3624232851164377625821465723291164
 27257351286885786434514725741287
 32298101490599377453596229811491
 403636018180121209090727236361818
42273478517393115958696695734791739
 3240335201681344510084806740342017
 4049235246181641212309984749242462
 48581602908019387145401163258162908
482745060225301502011265901245062253
 32523102615517437130781046252312616
 40639603198021320159901279263963198
 48755853779325195188961511775593779

Table 4( Part B : Air Velocity (fpm) ). Total air volume and air velocity through the grain for grain bins with 37 degree cones. (cont'd)

         
   Air Velocity (fpm)
   Air Flow Rate (cfm/bu)
Diameter (ft.)Height (ft.)Total Capacity
(Bin+Cone), bu
2-Jan3-Jan4-Jan5-Jan10-Jan20-Jan
15813953.952.631.971.580.790.39
 1321206432.41.20.6
 1625457.24.83.62.881.440.72
181127005.313.542.652.121.060.53
 1331006.094.063.052.441.220.61
 1637257.324.883.662.931.460.73
 2147509.346.234.673.741.870.93
211343456.284.183.142.511.260.63
 1651707.474.983.732.991.490.75
 24739510.687.125.344.272.141.07
241669057.645.093.823.051.530.76
 1979808.825.884.413.531.760.88
 24980510.847.235.424.342.171.08
 321270514.059.377.025.622.811.4
2719102908.995.994.53.61.80.9
 241256510.987.325.494.392.21.1
 321626514.219.477.115.682.841.42
3019128959.136.084.563.651.830.91
 241574511.147.435.574.462.231.11
 322029514.369.587.185.752.871.44
33241936511.337.555.664.532.271.13
 272144012.548.366.275.022.511.25
 322486514.549.77.275.822.911.45
36242328511.447.635.724.582.291.14
 272573512.658.436.325.062.531.26
 322981014.659.777.335.862.931.47
 403636017.8711.918.937.153.571.79
42273478512.568.376.285.022.511.26
 324033514.569.717.285.832.911.46
 404923517.7811.858.897.113.561.78
 4858160211410.58.44.22.1
48274506012.468.36.234.982.491.25
 325231014.469.647.235.782.891.45
 406396017.6811.798.847.073.541.77
 487558520.913.9310.458.364.182.09

Example: Using our sample bin (30 ft. diameter and 19 ft. height), suppose we wish to provide an airflow rate of 1/5 (0.2) CFM/bu. Table 3 gives a total air volume of about 2719 CFM and an air velocity through the grain of 3.85 fpm.  If the cone bottom has a 37° cone, use Table 4.

Determining Operating Static Pressure Due to Grain Depth

Tables 5, 6, 7, 8, and 9 can be used to determine the static pressure due to grain depth when the grain depth or bin sidewall height and the air flow rate through the grain are known. It is assumed the bin will be filled to the eaves and the top surface will be leveled, making grain depth and bin sidewall height equal. Table 5 is used when shelled corn is the grain to be aerated, Table 6 is used for barley and oats, Table 7 for soybeans and confectionary sunflowers, Table 8 for oil-type sunflowers and Table 9 for wheat and sorghum. The static pressure of canola is two to three times the static pressure of wheat. Therefore, if an existing aeration system designed for wheat is used for canola, check the velocity and pressure ratings of the system to ensure adequate airflow. Fact Sheet BAE-1110, “Storing Oklahoma Winter Canola,” covers the methods for storing Oklahoma winter canola. When the system will be used for more than one grain, design for the grain that gives the highest expected static pressure.

Table 5. Expected Static Pressure for shelled corn. 
Values in the table have been multiplied by 1.5 to account for fines and packing in the bin. (If corn is stirred, which tends to decrease airflow resistance, divide table values by 1.5.)
Expected static pressure (inches of water)

Grain depth (ft)0.050.10.250.50.7511.251.52
20.10.10.10.10.10.10.10.10.1
40.10.10.10.10.10.10.10.20.2
60.10.10.10.10.20.30.30.40.6
80.10.10.10.20.30.50.60.81.2
100.10.10.20.30.50.81.11.42
120.10.10.20.50.81.21.62.13.2
140.10.10.30.71.21.72.334.6
160.10.10.40.91.62.43.24.26.4
180.10.20.51.22.13.14.35.68.7
200.10.20.71.62.745.67.311.3
250.20.41.12.64.679.712.819.9
300.30.51.64.17.21115.320.331.9
400.513.18.114.622.631.942.5*
500.71.65.31425.639.9***

* Static pressure is excessive--greater than 50 in. water.

Table 6. Expected Static Pressure for barley and oats. 

Values in the table have been multiplied by 1.5 to account for fines and packing in the bin.
Expected static pressure (inches of water)

Grain depth (ft)0.050.10.250.50.7511.251.52
    Airflow (cfm/bu)            
20.10.10.10.10.10.10.10.10.1
40.10.10.10.10.20.20.30.30.5
60.10.10.10.20.40.50.70.81.1
80.10.10.20.40.70.91.21.52.1
100.10.10.30.71.11.522.53.6
120.10.20.511.62.333.75.4
140.10.30.71.42.23.24.25.37.8
160.20.30.91.934.35.77.210.6
180.20.41.12.43.95.67.59.514.1
200.30.51.434.97.19.512.218.1
150.40.82.24.98.211.916.120.731.1
300.61.23.27.412.418.324.832.148.7
4012.1614.224.436.249.8**
501.63.49.923.841.4****

* Static pressure is excessive--greater than 50 in. water.

Table 7. Expected Static Pressure for soybeans and confectionary sunflowers. 
Values in the table have been multiplied by 1.5 to account for fines and packing in the bin.
Expected static pressure (inches of water)

Grain depth (ft)0.050.10.250.50.7511.251.52
 Airflow (cfm/bu)      
20.10.10.10.10.10.10.10.10.1
40.10.10.10.10.10.10.10.10.2
60.10.10.10.10.20.20.30.30.5
80.10.10.10.20.30.40.50.60.9
100.10.10.10.30.40.60.811.5
120.10.10.20.40.70.91.21.62.3
140.10.10.30.60.91.31.72.23.3
160.10.10.30.81.21.82.434.5
180.10.20.411.62.33.146
200.10.20.61.22345.17.7
250.20.30.923.456.88.813.4
300.20.51.33.15.27.710.613.721
400.40.92.55.910.315.421.42843.4
500.61.44.11017.626.737.249.1*

* Static pressure is excessive--greater than 50 in. water.

Table 8. Expected Static Pressure for oil-type sunflowers. 

Values in the table have been multiplied by 1.5 to account for fines and packing in the bin.
Expected static pressure (inches of water)

Grain depth (ft)0.050.10.250.50.7511.251.52
    Airflow (cfm/bu)     
20.10.10.10.10.10.10.10.10.1
40.10.10.10.10.10.20.20.20.3
60.10.10.10.20.30.40.50.60.9
80.10.10.10.30.50.70.91.11.7
100.10.10.20.50.81.11.51.92.8
120.10.10.30.71.21.72.32.94.4
140.10.20.511.72.43.34.26.4
160.10.20.61.42.33.34.55.88.8
180.10.30.81.834.467.811.8
200.20.312.33.85.67.71015.3
250.30.61.63.76.59.713.317.426.9
300.40.82.45.71015.120.927.542.7
400.71.54.511.320.130.743**
501.12.47.519.334.8****

* Static pressure is excessive--greater than 50 in. water.

Table 9. Expected Static Pressure for wheat and sorghum.
Values in the table have been multiplied by 1.3 for wheat and 1.5 for sorghum to account for fines and packing in the bin.
Expected static pressure (inches of water)

Grain depth (ft)0.050.10.250.50.7511.251.52
    Airflow (cfm/bu)             
20.10.10.10.10.10.10.10.10.2
40.10.10.10.20.30.30.40.50.7
60.10.10.20.40.60.811.21.7
80.10.10.30.71.11.51.92.33.2
100.10.20.51.11.72.333.75.3
120.10.30.81.62.53.44.55.67.9
140.20.412.23.44.86.37.811.3
160.30.51.42.94.66.48.410.615.3
180.30.71.73.75.98.31113.820
200.40.82.24.77.510.513.917.625.6
250.61.33.47.512.217.423.129.443.3
300.91.95.111.218.326.335.345*
401.73.49.321.135.1****
502.65.41534.8*****

* Static pressure is excessive--greater than 50 in. water.

Example:To design the system for our sample bin (19 ft. height) to store either corn or soybeans, consider both Table 5 and Table 7. Since the tables do not give data for 0.2 cfm/bu airflow rates, use the next higher airflow given. In this case, we would use 0.25 cfm/bu. The tables do not give data for 19 ft. height either, so we would calculate the static pressure that would be halfway between the pressures shown for 18 ft and 20 ft heights.

For corn (Table 5):  at 18 ft grain depth, pressure = 0.5 in. and at 20 ft., pressure = 0.7 in. Therefore, at 19 ft. grain depth, the pressure will be 0.6 in. or halfway between 0.5 and 0.7 in.

For soybeans (Table 7):  at 18 ft grain depth, pressure = 0.4 in. and at 20 ft., pressure = 0.6 in. Therefore, at 19 ft. grain depth, the pressure will be 0.5 in.

Since we would like to design our system to handle either crop, we must design for the greater pressure requirements.  In this case, it would be corn and we would use 0.6 in. for our pressure requirement due to grain depth.

Determining Static Pressure Due to Duct and Cone

Pressure requirements are also increased due to air traveling through the air ducts.  To find these pressure requirements, the surface area of the ductwork must be known.  Table 10 gives the duct surface area given the duct diameter and the duct length. Tables 11 and 12 use the surface area from Table 10 and the air-flow volume calculated earlier to determine the expected static pressure for the duct system and for the airflow through the cone part of the bin.  This pressure added to the pressure for the grain depth is the design pressure used to select the aeration fans.

Table 10. Duct Surface Area.

Duct Diameter
(inches)
Duct Length
(ft)
Duct Surface Area
(Sq. ft.)
61013
 1519
 2025
 2531
 3038
 3544
101021
 1531
 2042
 2552
 3063
 3573
121025
 1538
 1845
 2050
 2563
 3075
 3588
151031
 2063
 2579
 3094
 35110
181038
 1557
 2075
 2594
 30113
 35132
201042
 1563
 2084
 25105
 30126
 35147
241050
 1575
 20100
 25126
 30151
 35176
301063
 1594
 20126
 25157
 30188
 35220
361075
 15113
 20151
 25188
 30226
 35264
401084
 15126
 20167
 25209
 30251
 35293

Table 11. Expected static pressure due to duct and cone for corn or soybeans. 
Expected Static Pressure (inches of water)

 Total Air Volume (CFM)
Duct Surface Area (sq. ft.)100500100020003000 4000 5000 6000 70008000100002000030000
100.262.57.5** * * * *****
150.151.43.910*********
200.10.912.56*********
30**0.541.43.76.5********
40**0.350.922.54.46.48.5******
50**0.260.71.753.256.88.5*****
60**0.210.551.452.453.85.16.88****
80**0.140.270.941.72.53.354.455.46.58.6**
100**0.10.260.691.31.82.53.33.94.76.3**
150****0.160.390.71.11.451.92.32.73.6**
200****0.120.270.46 0.65 0.75 1.3 1.51.82.66.5*
300******0.150.27 0.39 0.5 0.7 0.851.051.493.756.8

** Static pressure is less than 0.1 in. water.
*Static pressure is excessive--greater than 10 in. water.

Table 12. Expected static pressure due to duct and cone for wheat, grain sorghum, oats, barley, or rye.

Duct Surface Area (sq.  ft.)10050010002000300040005000600070008000100002000030000
100.85.513**********
150.493.47.9**********
200.352.45.512*********
30**1.453.47.812.8********
40**12.45.5912.5*******
50**0.81.854.26.81013******
60**0.651.53.455.47.910.11315****
80**0.450.82.43.85.57910.812.5***
100**0.350.791.82.94.35.578.19.512.2**
150****0.51.11.82.553.44.44.95.87.5**
200****0.370.81.31.82.433.54.25.612.9*
300******0.50.840.121.51.852.22.63.457.913

 ** Static pressure is less than 0.3 in. water.
*Static pressure is excessive--greater than 15 in. water. 

Example:

  1. For the sample bin using 12 in. duct diameter and 18 ft. duct length, the duct surface area is 45 sq. ft. (Table 10). 
  2. Using Table 11 for corn or soybeans, 45 sq. ft. duct surface area, and 2719 cfm (rounded up to 3000 cfm) air volume, the static pressure due to the duct system and the cone is 3.8 in. (use pressure half way between 40 sq. ft. and 50 sq. ft. since there is not data for 45 sq. ft) 
  3. For the total pressure requirement, add the pressure due to grain depth and the pressure through the cone and duct system:  0.5 in. + 3.8 in. = 4.3 in.

When the bin will be used to store more than one grain, the grain which produces the highest static pressure should be used for design purposes. The static pressure of canola is two to three times that of wheat.

The static pressure due to duct and cone can be reduced by choosing a larger diameter duct. Table 13 compares the re­sults obtained for a 12-inch diameter duct with those obtained for 18- and 21-inch diameter ducts.

Selecting Fans

Fans are selected from the manufacturer's rating curves or tables to deliver the required air volume when operating against the expected static pressure. Axial fans (propeller-type) are commonly used for aeration since they produce high air volumes at low static pressures. However, air volumes delivered by axial fans fall off rapidly as static pressures in­crease through the 3.5 to 5.0 inch range. Above this range, centrifugal fans with backward-inclined blades must be used.  In special designs, centrifugal fans will operate efficiently at static pressures of 20 inches or more.

Centrifugal fans operate with less noise than axial fans and should be used whenever fan noise may be a nuisance to neighbors. Centrifugal fans of 3 Hp or less cost two to three times as much as axial fans of the same Hp rating. Above 5 Hp, centrifugal fans cost 1.5 to 2 times as much as axial fans of the same Hp rating.

The lowest priced fan which will deliver the required air volume when operating at the expected static pressure is, of course, the most economical fan to buy. However, the most economical fan to operate is the fan with the lowest power consumption, measured in watts, while delivering the required air volume at the expected static pressure. Nominal horse­power rating is not a good measure of power consumption.

While final fan selection must be made from manu­facturer's data, an estimate of the power requirement may be helpful for planning purposes. Equation 1 is used to estimate the power requirement, assuming a fan efficiency of 50 percent.

  hp = (cfm x Ps) ÷ (63.46 x efficiency)                               equation 1

  where:

  cfm = airflow in cfm

  Ps = static pressure in inches of water

  efficiency = fan efficiency (%)

Example: Our example calls for an air volume of 2719 CFM. If the operating pressure is 4.3 inches, the power requirement is about 3.68 Hp (select a 5 HP motor). Table 13 also compares the power requirements resulting from the use of a 12-inch diameter duct with those resulting from the use of 18- and 24-inch diameter ducts.

When selecting fans, consult the data from several manu­facturers. Tables 14 and 15 present typical performance data for axial and centrifugal fans, respectively. One manufacturer's 5 Hp fan may be well matched to your needs while another's 5 Hp fan may not. Fan performance data should be certified in accordance with standard test codes adopted by Air Moving and Conditioning Association, Incorporated and bear the AMCA seal.

Table 13. Static Pressures and Power Requirements resulting from three duct diameters in the example.

 Duct Diameter (inches)
 121824
Maximum length of Perforated Duct (ft)181716
Static Pressure due to Duct and Cone (inches of water) For Corn or Soybeans3.821.5
Total Static Pressure (inches of water)
For Corn or Soybeans
4.32.62.1
Power Required assuming 50% efficiency (Hp) For Corn or Soybeans3.72.21.8

Table 14. Typical Performance Data for Axial Fans*.

 Static Pressure (Inches of water) 
CFM 
HPRPM0.511.5234 
134502880263523601935810455 
33450700064005700520037002200 
53450970091008600800065004600 
7.534501280012300116001100098007400 

 *This table is abbreviated. Intermediate static pressures and a much larger range of CFM values are normally shown

Table 15A. Typical Performance Data for Centrifugal Fan*. 

Static Pressure (inches of water)

CFM2 RPM2 HP4 RPM3 HP6 RPM6 HP8 RPM8 HP10 RPM10 HP12 RPM12 HP14 RPM14 HP
152013641.1517531.9620642.7723323.625744.4727945.3730006.3
202615271.8118942.8921903.9424464.9926796.0528917.1430908.25
253217082.7220504.0723345.425846.7128058.0130109.3320410.6
303919063.9322215.524907.1527308.75294610.3314511.8333313.4

 *This table is abbreviated. Intermediate static pressures and a much larger range of CFM values are normally shown. Various speeds may be obtained using variable frequency drives or belt and sheave systems between a roteor and fan. Typical motor operating speeds are 1,760 rpm and 3,500 rpm (nominal).

Further Examples

Example 1:  An aeration system is desired for a 24 feet diameter bin with 16 feet sidewalls and 37˚ cone shaped foundation which will be used to store wheat. An airflow rate of 1/4 (0.25) CFM/bu is desired.

  1. Bin capacity is 6905 bu (Table 1).  Airflow volume:  6905 bu x 0.25 CFM/bu = 1726 CFM (also in Table 4).
  2. From Table 2, maximum duct length is 14 feet.
  3. Air velocity through the grain is 3.82 fpm (Table 4). The static pressure due to the 16 feet grain depth is 1.4 inches (Table 9).
  4. Maximum perforated duct if an 18 in. dia. duct is selected:  14 ft – (2 x 1.5 ft) = 11 ft.
  5. Duct surface area: The duct surface area of 10ft and 15ft duct is known (Table 10).  Estimate for 11ft duct length using interpolation:|
    38+((11-10)*(57-38)/(15-10)) = 38+ 3.8= 42 sq. ft.  (Table 10).
  6. Static Pressure due to cone and duct, as static pressure for 1726 cfm and 42 sq ft area is not given directly in Table 12 therefore we calculate the static pressure for  2000 cfm and 42 sq ft by interpolation:
       5.5 + ((42-40)*(4.2-5.5)/ ((50-40)) = 5.24 in. of water (Table 12).
  7.  Total static pressure:  5.24 + 1.4 in. = 6.64. 
  8.  Approx. HP:  hp = 
    (1726 * 6.64) / (63.46 * 50) = 3.61 HP         (equation 1) 
  9.  Choose a 5 HP fan.

Example 2: Suppose a producer wishes to provide 1/2 (0.5) CFM/bu. for quick cooling of damp corn during harvest. The bin is 27 feet in diameter, has 24 feet sidewalls and a 45˚ cone shaped foundation.

  1. Bin capacity is 13085 bu (Table 1).  Airflow volume:  13085 bu x 0.50 CFM/bu = 6543 CFM (also in Table 3).
  2. From Table 2, maximum duct length is 18 feet.
  3. Air velocity through the grain is 11.43 fpm (Table 3). The static pressure due to the 24 feet grain depth is 2.4 inches (Table 5).
  4. Maximum perforated duct:  If 30 in duct is selected, round up to 3 feet, 18 ft – (2 x 3 ft) = 13 ft.
  5. Duct surface area, using interpolation and Table 10:
    63 + ((13-10) x (94-63) / (15-10)) = 63+18.6 =
    81.6 Sq. ft.= 82 Sq. ft.  (Table 10).
  6.  Pressure due to cone and duct, as static pressure for 6543 cfm and 82 sq ft area is not given directly in Table 11 therefore we calculate the static pressure for  7000 cfm and 75.4 sq ft by interpolation:
       5.4 + ((82-80) x (3.9-5.4) / (100-80)) = 5.25  (Table 11)
  7. Total static pressure:  5.25 + 2.4 in. = 7.65.
  8. Approx. HP :hp= (6543 x 7.65) / (63.46 x 50)=15.8 HP                          (equation 1).
  9. Choose a 20 HP fan

Other Considerations

Aeration systems for cone-bottom bins must operate as pressure systems-blowing air upward through the grain. For more information about pressure and suction systems, see BAE-1101.

There must be sufficient roof openings to allow the air to escape. The required air escape area, in square feet, is determined by dividing the total air volume by 1,500 fpm. If the bin roof is mounted off the sidewall, the slot under the eaves serves as air escape area. When additional area is required, roof vents should be installed until the air escape area requirement is met.

When aeration systems are operating, the unloading auger tube should be sealed to prevent the escape of air.

Smooth transitions should be used to connect fan outlets with duct inlets. Sudden reductions or increases in duct diameters should be avoided.

Carol Jones
Extension Agricultural Engineer

Was this information helpful?
YES NO

No results to display

VIEW ALL